Informacja

Drogi użytkowniku, aplikacja do prawidłowego działania wymaga obsługi JavaScript. Proszę włącz obsługę JavaScript w Twojej przeglądarce.

Tytuł pozycji:

Voltage Reduction in Medium Voltage Distribution Systems Using Constant Power Factor Control of PV PCS

Tytuł:
Voltage Reduction in Medium Voltage Distribution Systems Using Constant Power Factor Control of PV PCS
Autorzy:
Daisuke Iioka
Takahiro Fujii
Toshio Tanaka
Tsuyoshi Harimoto
Junpei Motoyama
Temat:
distributed power generation
photovoltaic systems
power quality
power distribution
power system analysis computing
power system measurements
Technology
Źródło:
Energies, Vol 13, Iss 20, p 5430 (2020)
Wydawca:
MDPI AG, 2020.
Rok publikacji:
2020
Kolekcja:
LCC:Technology
Typ dokumentu:
article
Opis pliku:
electronic resource
Język:
English
ISSN:
1996-1073
Relacje:
https://www.mdpi.com/1996-1073/13/20/5430; https://doaj.org/toc/1996-1073
DOI:
10.3390/en13205430
Dostęp URL:
https://doaj.org/article/e6bf792f85444b099c9d475aff044cd0  Link otwiera się w nowym oknie
Numer akcesji:
edsdoj.6bf792f85444b099c9d475aff044cd0
Czasopismo naukowe
Reverse power flow from a photovoltaic (PV) system in a distribution system causes a voltage rise. A relative study regarding the reduction in the distribution feeder voltage depending on system conditions and the magnitude of reverse power flow has been conducted. Several methods for mitigating voltage rise have been proposed; however, the influence of these methods on the voltage in the distribution system, where the voltage is reduced due to reverse power flow, remains to be determined. In this study, the effect of constant power factor control in low-voltage PV systems, which are widely used as voltage rise countermeasures in distribution systems, was analyzed under the condition that the distribution line voltage decreases due to reverse power flow. Consequently, the constant power factor control of the low-voltage distribution system was found to adversely reduce voltage in the medium voltage distribution system due to the consumption of lagging reactive power by the PV systems.
Zaloguj się, aby uzyskać dostęp do pełnego tekstu.

Ta witryna wykorzystuje pliki cookies do przechowywania informacji na Twoim komputerze. Pliki cookies stosujemy w celu świadczenia usług na najwyższym poziomie, w tym w sposób dostosowany do indywidualnych potrzeb. Korzystanie z witryny bez zmiany ustawień dotyczących cookies oznacza, że będą one zamieszczane w Twoim komputerze. W każdym momencie możesz dokonać zmiany ustawień dotyczących cookies